Voltage Drop Calculator

Estimate voltage drop on a copper or aluminum wire run by AWG size and length in feet, with the percentage drop and the voltage at the load.

Written by Ahmet Tur · Reviewed by Kübra Yıldız · Updated

75 °C matches NEC Chapter 9, Table 8 resistances

Your result will appear here

Fill in the fields and press Calculate.

Voltage drop on a single-phase or DC circuit is VD = I × R, where R is the resistance of the conductor out and back: R = ρ × 2L ÷ A. A 16 A load at the end of 100 feet of 12 AWG copper on a 120 V circuit loses about 6.2 V (5.1%) with the conductor at 75 °C, the temperature behind the NEC Chapter 9, Table 8 resistances, and about 5.1 V (4.2%) for a cool conductor at 20 °C.

Enter the current, the one-way length in feet (or meters), the wire size from 18 AWG to 4/0, copper or aluminum, the conductor temperature (75 °C by default) and the supply voltage (120 V by default). It returns the drop in volts, the drop as a percentage of the source voltage, the voltage left at the load and the conductor area in mm² behind the gauge.

The often-quoted 3% and 5% limits are recommendations in National Electrical Code informational notes, not enforceable requirements, but a few NEC articles and federal design criteria do set mandatory limits. This page shows exactly which, why different calculators give different answers for the same wire, and how to bring an excessive drop down. It is a design estimate; final conductor sizing belongs to a qualified electrician and your local authority having jurisdiction.

Voltage Drop Calculator: step-by-step worked example

Example inputs
Current (A)
16
One-way length (ft)
100
Wire size (AWG)
12 AWG
Conductor
Copper
Conductor temperature (°C)
75
Source voltage (V)
120
  1. 1

    Conductor resistivity at temperature

    ρT = ρ20 × (1 + α × (T − 20)) · copper ρ20 0.0172, α 0.00393 · aluminum ρ20 0.0282, α 0.00403

    0.0172 × (1 + 0.00393 × (75 − 20)) = 0.0209 Ω·mm²/m

  2. 2

    Convert length to metres

    L (m) = L (ft) × 0.3048

    100 × 0.3048 = 30.48 m

  3. 3

    AWG size to mm²

    A = cmil × π/4 × 0.0254² (ASTM B258)

    12 AWG = 6,530 cmil = 3.3088 mm²

  4. 4

    Round-trip cable resistance

    R = ρT × (2 × L) ÷ A

    0.020918 × (2 × 30.48) ÷ 3.3088 = 0.3854 Ω

  5. 5

    Voltage drop

    ΔV = I × R

    16 A × 0.3854 Ω = 6.1661 V

  6. 6

    Percentage drop

    %ΔV = ΔV ÷ Source voltage × 100

    6.1661 ÷ 120 × 100 = 5.14%

  7. 7

    Voltage at the load

    V load = Source − ΔV

    120 − 6.1661 = 113.83 V

Result · Voltage drop6.1661 V
Voltage from source to load
  • Source120 V
  • Cable drop−6.1661 V
  • At load113.83 V
AmountDeduction
Percentage drop by cable size
  • 14 AWG8.16%
  • 12 AWG5.14%
  • 10 AWG3.23%
  • 8 AWG2.03%
  • 6 AWG1.28%
  • 4 AWG0.8%

Good to know: Length is the one-way run; the formula doubles it for the return conductor (single-phase). Resistance is corrected to the conductor temperature — 75 °C reproduces NEC Chapter 9, Table 8 (12 AWG copper ≈ 1.93 Ω per 1,000 ft). NEC informational notes suggest ≤ 3% on a branch circuit and ≤ 5% overall — upsize the wire if you exceed it.

Voltage Drop Calculator — how it works

The formula the calculator uses

For a two-wire run, current flows out on one conductor and back on the other, so the resistance is that of twice the one-way length:

R = ρ × (2 × L) ÷ A, then VD = I × R, % drop = VD ÷ V × 100, V at load = V − VD

where ρ is resistivity in Ω·mm²/m, L the one-way length in meters (feet × 0.3048), A the cross-section in mm², I the current in amperes and V the source voltage. The calculator starts from ρ = 0.0172 for copper and 0.0282 for aluminum at 20 °C and corrects it to the conductor temperature T: ρT = ρ20 × (1 + α × (T − 20)), with α = 0.00393 per °C for copper and 0.00403 for aluminum. AWG sizes are converted with the ASTM B258 circular-mil areas (1 circular mil = 0.0005067 mm²). That copper figure is the conventional value for annealed conductor copper; pure copper is slightly lower, 1.68 × 10⁻⁸ Ω·m (0.0168 Ω·mm²/m) in Georgia State University's HyperPhysics table. Aluminum's figure is about 1.64 times copper's, which is why aluminum feeders are usually sized larger.

The model is DC resistance only. It ignores conductor reactance and power factor, which add to the drop on large AC conductors and motor loads. For a balanced three-phase circuit, the multiplier is √3 (1.732) instead of 2, so you can multiply this calculator's single-phase result by 0.866 to estimate the line-to-line drop for the same per-phase current and length.

AWG sizes, areas and resistance

AWGmm²Circular milsΩ per 1,000 ft at 20 °CΩ per 1,000 ft at 75 °C
142.084,1102.523.06
123.316,5301.581.93
105.2610,3801.001.21
88.3716,5100.630.76
613.326,2400.390.48
421.241,7400.250.30
233.666,3600.160.19
1/053.5105,6000.0980.12
2/067.4133,1000.0780.095
4/0107211,6000.0490.060

Copper, per conductor, as this calculator computes it. Areas are the ASTM B258 nominal values; the 75 °C column matches NEC Chapter 9, Table 8 for solid uncoated copper (stranded wire runs about 2–3% higher, e.g. 1.98 Ω for 12 AWG).

Why 75 °C results come out 20–25% higher

Conductor resistance rises with temperature. HyperPhysics gives copper's temperature coefficient as 0.00386 per °C, so warming from 20 °C to 75 °C adds roughly 21% before stranding effects. US practice uses the DC resistances in NEC Chapter 9, Table 8, which are stated at 75 °C. The International Association of Electrical Inspectors (IAEI) expresses them as a K factor for the classic formula VD = 2 × K × I × L ÷ CM (L in feet, CM in circular mils): K = 12.9 for uncoated copper and 21.2 for aluminum.

This calculator applies that correction itself. At the default 75 °C its copper resistance is about 21.6% above the 20 °C value, equivalent to K ≈ 12.6 for solid copper (the IAEI's 12.9 reflects stranded conductors); set the temperature to 20 °C to reproduce a cool-conductor calculation. The assumed temperature is the main reason two voltage drop calculators can disagree on the same circuit: one is modeling a cool conductor, the other a conductor at its 75 °C rating.

What the NEC actually says about 3% and 5%

The NEC's voltage drop percentages sit in informational notes. The note to the branch-circuit conductor rules (210.19) says conductors sized to prevent a drop exceeding 3% at the farthest outlet, with a maximum total of 5% for feeders and branch circuits combined, provide reasonable efficiency of operation; the feeder rules (215.2) carry a parallel note. Section 90.5 states that informational notes are explanatory and not enforceable as requirements, so a circuit at 4% does not by itself violate the NEC.

Mandatory limits do exist in specific places:

  • Fire pumps (695.7): the voltage at the controller line terminals must not drop more than 15% during motor starting, and the voltage at the motor terminals must not drop more than 5% while running at 115% of full-load current.
  • Sensitive electronic equipment (Article 647): sets a branch-circuit limit as low as 1.5%.
  • Phase converters (455.6): require a voltage drop check as part of conductor sizing.
  • Federal military construction: UFC 3-501-01 (2024) makes the limits mandatory for its projects: feeders and service conductors 3%, branch circuits 3%, and no more than 5% total, measured from the point of government ownership.

Local amendments and energy codes may also adopt limits, so the controlling number is whatever your authority having jurisdiction enforces.

Bringing an excessive drop down

The drop scales with current and length and inversely with conductor area, which gives four levers. UFC 3-501-01 lists the same ones: increase conductor size, reduce the load, shorten the run, lower conductor temperature and improve power factor.

ChangeEffect on the drop
12 AWG → 10 AWG copper−37% (area 3.31 → 5.26 mm²)
12 AWG → 8 AWG copper−60%
Halve the run length−50%
Same current at 240 V instead of 120 Vvolts unchanged, % drop halves
Same power at 240 V instead of 120 Vcurrent halves, so % drop falls to one quarter
Aluminum instead of copper, same size+64%

Upsizing for voltage drop does not change the ampacity rules: the wire still has to meet the NEC ampacity and termination requirements for its overcurrent device, and, per UFC 3-501-01, an equipment grounding conductor is increased in proportion when phase conductors are upsized for voltage drop (NEC 250.122).

Limits of this estimate

The calculator gives the steady-state resistive drop of one run. It does not include upstream feeder drop (add the percentages to check the 5% total), transformer regulation, motor inrush, reactance or connection resistance, and it assumes the whole run is at the temperature you enter. For anything that will be inspected, use NEC Chapter 9 values or ask a licensed electrician.

Worked example

You are feeding a detached garage 100 feet from the panel on a 120 V, 20 A circuit, and the load will draw 16 A for hours at a time. You are considering 12 AWG copper.

Enter 16 A, 100 ft, 12 AWG, copper, 75 °C and 120 V. 12 AWG is 6,530 circular mils = 3.309 mm², copper at 75 °C has ρ = 0.0172 × (1 + 0.00393 × 55) = 0.02092 Ω·mm²/m, and 100 ft is 30.48 m each way. The run resistance is 0.02092 × (2 × 30.48) ÷ 3.309 = 0.3854 Ω, so the drop is 16 × 0.3854 = 6.17 V, or 5.14%, leaving 113.83 V at the garage. At 20 °C it would be 5.07 V (4.23%). Either way it is above the 3% branch-circuit recommendation.

Switch to 10 AWG: 3.88 V, 3.23% at 75 °C (2.66% at 20 °C). At 8 AWG: 2.44 V, 2.03% (1.67% at 20 °C), which leaves room for feeder drop under the 5% total.

If the load could run at 240 V with the same 16 A, 12 AWG would show the same 6.17 V but only 2.57% of 240 V. Ampacity, breaker size and terminations still have to follow the NEC.

Frequently asked questions

How do you calculate voltage drop?+

Multiply the current by the resistance of the conductor out and back: VD = I × ρ × 2L ÷ A. In US units the same formula is VD = 2 × K × I × L ÷ CM, with K = 12.9 for copper at 75 °C, L in feet and CM in circular mils.

Is a 3% voltage drop required by the NEC?+

No. The 3% branch-circuit and 5% total figures are in informational notes (210.19 and 215.2), which section 90.5 says are not enforceable. Specific articles such as 695.7 for fire pumps and 647 for sensitive electronic equipment do set mandatory limits, and local codes may too.

What is the voltage drop on 100 feet of 12 gauge wire at 16 amps?+

About 6.2 V (5.1%) on a 120 V circuit with the conductor at 75 °C (the NEC Chapter 9 basis), or about 5.1 V (4.2%) at 20 °C. On 10 AWG it is about 3.2 to 3.9 V, roughly 2.7% to 3.2%.

Why do different voltage drop calculators give different answers?+

Mostly because of the assumed conductor temperature. NEC Chapter 9 Table 8 resistances are at 75 °C, about 20–25% higher than 20 °C values; this calculator lets you set the temperature and defaults to 75 °C. Some calculators also include reactance and power factor.

How does the calculator turn an AWG size into mm²?+

It uses the ASTM B258 circular-mil areas: 14 AWG = 2.08 mm², 12 AWG = 3.31 mm², 10 AWG = 5.26 mm², 8 AWG = 8.37 mm², 6 AWG = 13.3 mm². Just pick the gauge; the length can be entered in feet or meters.

Does voltage drop depend on whether the circuit is 120 V or 240 V?+

The drop in volts depends only on current and resistance, but the percentage is relative to the supply. The same 5 V is 4.2% of 120 V and 2.1% of 240 V, and the same power at 240 V draws half the current.

How do I calculate three-phase voltage drop?+

Replace the factor 2 with √3 (1.732): VD = 1.732 × I × R per conductor length. With this calculator, multiply the single-phase result by 0.866 for the same current and run length.

Should I enter the one-way or round-trip length?+

One-way. The calculator doubles it to account for the return conductor. Entering the round-trip distance would double the result.

Does aluminum wire have more voltage drop than copper?+

Yes, about 64% more at the same size, because its resistivity is 0.0282 versus 0.0172 Ω·mm²/m. That is why aluminum conductors are typically one or two sizes larger than copper for the same run.

Sources

About this page

Publisher:
Kalkoro — Teknolojig Bilişim Teknolojileri A.Ş., İstanbul
Written by:
Ahmet Tur — Editor (Math, date & time, unit conversion, physics & chemistry, everyday tools)
Reviewed by:
Kübra Yıldız — Editor

Parameters come from official sources; the last update date is shown at the bottom of the page.

Spotted a wrong result? Use the "Report a bug" button at the top of the page; every report is reviewed.

How we calculate and our accuracy policy →

Results are for information only. For official matters the relevant authority's calculation prevails.

Last updated: