Voltage Drop Calculator

Estimate voltage drop over a copper or aluminium cable run, with the percentage drop and the voltage at the load.

Your result will appear here

Fill in the fields and press Calculate.

Every cable has resistance, so some voltage is lost along the way — a bigger issue on long runs, high currents and thin conductors. This calculator estimates that drop for a single-phase copper or aluminium run from the current, the one-way length and the conductor’s cross-section, and gives the voltage that actually reaches the load.

How is it calculated?

The calculation

Resistance of the run, then Ohm’s law:

R = ρ × (2 × length) ÷ area, then Vdrop = current × R

The 2× accounts for both conductors (out and back). ρ is the material’s resistivity:

ConductorResistivity (Ω·mm²/m)
Copper0.0172
Aluminium0.0282

Aluminium has about 60% higher resistance for the same size, so it drops more voltage.

Percentage drop and the 3% guideline

The percentage drop is Vdrop ÷ source voltage × 100. A common rule of thumb keeps voltage drop under about 3% for branch circuits (and ~5% overall), so equipment gets enough voltage. Exceed it and you fix it by using a larger conductor, a shorter run or a higher supply voltage.

Worked example

A 10 A load on a 50 m one-way run of 4 mm² copper: resistance is 0.0172 × (2 × 50) ÷ 4 = 0.43 Ω, so the drop is 10 × 0.43 = 4.3 V. On a 230 V supply that’s 1.87% — within the 3% guideline, leaving 225.7 V at the load. Switch to aluminium and the drop rises to about 7 V.

FAQ

How is voltage drop calculated?+

Find the run’s resistance — resistivity × (2 × one-way length) ÷ cross-section — then multiply by the current (Ohm’s law). The 2× covers the outgoing and return conductors. This tool does it for copper or aluminium.

What is an acceptable voltage drop?+

A widely used guideline keeps it under about 3% on a branch circuit and around 5% total from source to load, so equipment receives adequate voltage. Requirements vary by code and application, so treat this as a rule of thumb.

How do I reduce voltage drop?+

Use a larger conductor cross-section, shorten the cable run, reduce the current, or supply at a higher voltage. Increasing the conductor size is the most common fix, since drop is inversely proportional to cross-sectional area.

Why does aluminium drop more than copper?+

Because aluminium has a higher resistivity — about 0.0282 versus 0.0172 Ω·mm²/m for copper, roughly 60% more. For the same size and length it therefore has more resistance and a larger voltage drop, which is why aluminium runs are often sized up.

Does this cover three-phase systems?+

This estimate is for a single-phase two-wire run (the 2× length term). Three-phase drop uses a different factor (√3 instead of 2) and balanced-load assumptions, so for three-phase designs use a method suited to that.